| Temperature |
| Measurement range |
-10 ~ 80°C |
| Accuracy |
±0.2°C (0 ~ 60°C) |
| Repeatability |
±0.1°C |
| Response time |
< 5sec |
| Long term drift |
< 0.05°C/year |
| |
| Humidity |
| Measurement range |
0 ~ 100%RH |
| Accuracy * |
±1.8%RH (0 ~ 80%RH) |
| Repeatability |
±0.2%RH |
| Hysterisis |
< ±1%RH |
| Response time |
< 4sec |
| Long term drift |
< 0.5%RH /Year |
| |
| Dew point |
| Measurement range |
-40 ~ 60°C |
| Accuracy ** |
±4°C (-10 ~ 20°C) |
| |
| Common Specifications |
| Power supply |
8 ~ 28Vdc |
| Current consumption |
Max 3mA @24Vdc |
| Voltage outputs |
2-channels 0~1Vdc / 0~2.5Vdc / 0~5Vdc / 1~5Vdc
(Output impedance : 100Ω) |
| Current outputs |
1-channel 4-20mA
: Humidity range : 0 ~ 100%RH
: Temperature range : -40 ~ 80°C |
| Digital outputs |
RS485 2-wire half duplex (Modbus RTU protocol)
RS232 serial output (Modbus RTU protocol) |
| Filters |
Plastic grid filter with a built in stainless steel mesh
Plastic grid filter
Plastic grid filter with a built in PTFE membrane
Nickel coated sintered filter |
| Materials |
Body : Stainless steel (SUS304)
Filter : Cr coated PC/ABS plastic grid
Cable material : PUR |
| Operating temperature |
Temperature: -40 ~ 80°C, (Non condensation) |
| Storage temperature |
Temperature: -20 ~ 70°C, Humidity: Below 95%RH |
| Dimensions |
93mm x Ø12 |
| IP rating |
IP65 |
| Weight |
20g |